Providence Cardiovascular Lab Setback Analysis

Analysis: Energy model and Energy Trust of Oregon (ETO) Technical Analysis Report. Analysis for occupancy-based airflow setback in five cardiovascular laboratories served by a recirculating VAV air handler with hydronic reheat.

  • OpenStudio / EnergyPlus model of the cardiovascular laboratory suite and air handling system, including economizer, preheat, humidification, dehumidification, and VAV reheat controls

  • Determination of minimum unoccupied air change rates from room air change certification to maintain ASHRAE 170 positive pressure relationships

  • Development of occupancy schedules based on lab procedure windows, with setback during nights, weekends, and holidays

  • Evaluation of first cost and simple payback for:

  • Implement occupancy-scheduled VAV minimum airflow setback, reducing supply air from 15-23 ACH occupied to 6-10 ACH unoccupied

Analysis: Energy model and Energy Trust of Oregon (ETO) Technical Analysis Report. Analysis for occupancy-based airflow setback in five cardiovascular laboratories served by a recirculating VAV air handler with hydronic reheat.

Project Team

 

OWNER: PROVIDENCE PORTLAND MEDICAL CENTER
4805 NE Glisan Portland, Oregon 97213
Cylix Shane - Facilities Planner
Dennis Wallace - Facilities
Garth Didlick - Facilities
P: 503-215-1111

 

MECHANICAL ENGINEERING: RON ANDERSON CONTROLS INC
38515 Pit Road Philomath, OR 97330
Ron Anderson, PE
Alan Wright, PhD, PE
P: 541-740-4105

 

ANALYSIS: HELIX ENERGY PARTNERS LLC
113 Main Street, Helix, OR 97835
Michael Lovejoy, PE
P: 541-379-0271

 

ETO PROGRAM MANAGEMENT CONTRACTOR: TRC
Energy Trust of Oregon Existing Buildings
111 SW Columbia St, Suite 945 Portland, OR 97201
Waypoint Energy - Program Management Contractor
Austin Alvey Aguilera, EIT - Energy Advisor
Eric Tu - Engineering Manager
Ritesh Nayyar - Associate Director
P: 1-866-368-7878
existingbuildings@energytrust.org

bottom of page