Providence Cardiovascular Lab Setback Analysis
Analysis: Energy model and Energy Trust of Oregon (ETO) Technical Analysis Report. Analysis for occupancy-based airflow setback in five cardiovascular laboratories served by a recirculating VAV air handler with hydronic reheat.
OpenStudio / EnergyPlus model of the cardiovascular laboratory suite and air handling system, including economizer, preheat, humidification, dehumidification, and VAV reheat controls
Determination of minimum unoccupied air change rates from room air change certification to maintain ASHRAE 170 positive pressure relationships
Development of occupancy schedules based on lab procedure windows, with setback during nights, weekends, and holidays
Evaluation of first cost and simple payback for:
Implement occupancy-scheduled VAV minimum airflow setback, reducing supply air from 15-23 ACH occupied to 6-10 ACH unoccupied

Project Team
OWNER: PROVIDENCE PORTLAND MEDICAL CENTER
4805 NE Glisan Portland, Oregon 97213
Cylix Shane - Facilities Planner
Dennis Wallace - Facilities
Garth Didlick - Facilities
P: 503-215-1111
MECHANICAL ENGINEERING: RON ANDERSON CONTROLS INC
38515 Pit Road Philomath, OR 97330
Ron Anderson, PE
Alan Wright, PhD, PE
P: 541-740-4105
ANALYSIS: HELIX ENERGY PARTNERS LLC
113 Main Street, Helix, OR 97835
Michael Lovejoy, PE
P: 541-379-0271
ETO PROGRAM MANAGEMENT CONTRACTOR: TRC
Energy Trust of Oregon Existing Buildings
111 SW Columbia St, Suite 945 Portland, OR 97201
Waypoint Energy - Program Management Contractor
Austin Alvey Aguilera, EIT - Energy Advisor
Eric Tu - Engineering Manager
Ritesh Nayyar - Associate Director
P: 1-866-368-7878
existingbuildings@energytrust.org